Regulador de Voltaje MX321 para Generedor Stamford-> Especificaciones técnicas <- SENSING INPUTVoltage 190-264V ac max, 2 or 3 phase, Frequency 50-60 Hz nominalPOWER INPUT (PMG)Voltage 170-220V ac max, 3 phase, 3 wireCurrent 3A/phaseFrequency 100-120 Hz nominalOUTPUTVoltage max 120V dcCurrent continuous 3.7 AIntermittent 6A for 10 secs.Resistance 15 ohms minimumREGULATION+/- 0.5% THERMAL DRIFT0.02% perC change in AVR ambient (note 2)SOFT START RAMP TIME4 secondsTYPICAL SYSTEM RESPONSEAVR Response 10 msFiled current to 90% 80 msMachine Volts to 97% 300 msEXTERNAL VOLTAGE ADJUSTMENT+/-10% with 1 k ohm 1 watt trimmer (see note 3)UNDER FREQUENCY PROTECTIONSet point 95% Hz (see note 4)Slope 170% down to 30 HzUNIT POWER DISSIPATION12 watts maximumANALOGUE INPUTMaximum input +/- 5V dc (see note 5)Sensitivity 1v for 5% Generator Volts (adjustable)Input resistance 1k ohmQUADRATURE DROOP INPUT10 ohms burdenMax. sensitivity: 0.07 A for 5% droop 0PFMax. input: 0.33 AOVER EXCITATION PROTECTIONSet point 75 V dcTime delay 10 seconds (fixed)ENVIRONMENTALVibration 20-100 Hz 50mm/sec100Hz – 2kHz 3.3gOperating temperature -40 to +70oCRelative Humidity 0-70oC 95% (see note 6)Storage temperature -55 to +80oCTenemos disponibles mas productos para diferentes plantas de emergencia, no dudes en ContactarnosVISITA NUESTRA TIENDA Y ENCUENTRA MAS PRODUCTOS.https://eshops.mercadolibre.com.mx/NOVAR GENSET